GTH-85 Thermal Overload Relay

APPLICATION

The TOR protect the motors,Locking,Open phase(differential)

CHARACTERISTICS

Direct mounting structure
The TOR is mounting directly to the Magnetic Contactors without addtional brackets.(Applied model:GTH-22,40,85)      

Safety over
The finger proof safety cover prevent careless touch of electric conductor(Applied model:GTH-22,40,85)                      

Separation of power part and operation part
The main circuit and the operation part are separately designed and the operation part is commonly used in GTH-22,40,85

TYPES AND RATINGS

Ratings Type GTH-22 GTH-40 GTH-85
  Nominal current Ranges Ranges Ranges
    Min. Mid. Max. Min. Mid. Max. Min. Mid. Max.
Rated current(A) 0.14 0.1 0.14 0.16            
0.21 0.16 0.21 0.25            
0.33 0.25 0.33 0.4            
0.52 0.4 0.52 0.63            
0.82 0.63 0.82 1            
1.3 1 1.3 1.6            
2.1 1.6 2.1 2.5            
3.3 2.5 3.3 4            
5 4 5 6 4 5 6      
6.5 5 6.5 8 5 6.5 8      
7.5 6 7.5 9 6 7.5 9      
8.5 7 8.5 10 7 8.5 10 7 8.5 10
11 9 11 13 9 11 13 9 11 13
15 12 15 18 12 15 18 12 15 18
19 16 13 22 16 13 22 16 13 22
22       18 22 26 18 22 26
30       24 30 36 24 30 36
34       28 34 40 28 34 40
42             34 42 50
55             45 55 65
65             54 65 75
74             63 74 85
Element No. 2heaters Stanard Stanard Stanard
3heaters Option Option Option
Aux.contact 1NO1NC 1NO2NC 1NO3NC
Reset type Auto/Manual Auto/Manual Auto/Manual
Power consumption 1.8VA/Heater 2.0VA/Heater 3.5VA/Heater
Dimension(mm)(W*H*D) 44*63*90 53*67*90 70*73*103
Separate mounting unit AZ-22H AZ-40H AZ-85H
Other model 3heaters GTH-22/3 GTH-40/3 GTH-85/3
Differential GTK-22 GTK-40 GTK-85
Delay open GTH-22/L GTH-40/L GTH-85/L
Applied contactors   GMC-9,12,18,22 GMC-32,40 GMC-50,65,75,85
Applied switches   GMS-9,12,18,22 GMS-32,40 GMS-50,65,75,85