LE1-D09 12 18 Magnetic Starter

APPLICATION

LE1-D18 25 32 Magnetic Starter is mainly applied to circuit of AC 50 or 60Hz,voltage up to 550V for far distance making and breaking circuit and frequent start and control motor. It has the features of small volume, light, weight, low power consumption, high efficiency, safe and reliable perfomance etc.

SPECIFICATION

Maximum power AC3 duty(K W) Rated
current
(A)
Type of
enclosure
Code Number Suitable
Thermal
Relay(A)
220V 230V 380V 400V 415V 440V 500V 660V 690V LL
(Long life)
NL(3)
(normal life)   
1.1 2.2 22 22 ... ... 6 ... ... LE1 EC 135 LE1 EC135
2.2 4 4 4 5.5 5.5 9 IP42 IP65 LE1 D094...
LE1 D093...
... LR2 D1312
3 5.5 5.5 5.5 7.5 7.5 12 IP42 IP65 LE1 D124...
LE1 D123...
LE1 D094...  LE1 D093... LR2 D1314
4 7.5 9 9 10 10 18 IP42 IP65 LE1 D188...
LE1 D185...
LE1 D124...  LE1 D123... LR2 D 1316
5.5 11 11 11 15 15 25 IP42 IP65 LE1 D258...
LE1 D255...
LE1 D188...  LE1 D185... LR2 D 1321
7.5 15 15 15 18.5 18.5 32 IP55 LE1 D325... LE1 D255... LR2 D1322
LR2 D2353
11 18.5 22 22 22 30 40 IP55 LE1 D405... LE1 D325... LR2 D2355
15 22 25 30 30 33 50 IP55 LE1 D505... LE1 D405... LR2 D3353
LR2 D3355
18.5 30 37 37 37 37 65 IP55   LE1 D655... LE1 D505... LR2 D3357
LR2 D3359
22 37 45 45 55 45 80 IP55 LE1 D805... LE1 D655... LR2 D3363
LR2 D3365
25 45 45 45 55 45 95 IP55 LE1 D955... LE1 D805... LR2 D3365
Enclosure LE-D09 and D12 Double insulated, protected to IP 429 (3) or to IP659(4)
LE-D18 and D25 Double insulated, protected to IP 427 (3) or to IP577(4)
LE-D32...D25 Matel, IP 55 to IP 559
Control(2 pushbuttons mounted on    enclosure cover LE-D09...D95 1 green Start Button "1", 1 red Stop/Reset button "O"
Connections LE-D09...D95 Pre-wired power and contorl circuit connections
Standard control circuit voltages  
Voltages 24  42  48  110  220/230  230  240  380/400  400  415  440
50/60Hz B7    D7    E7    F7    M7    P7    U7    Q7   V7  N7  R7