1/2POLE Definite Purpose Contactor (20A THRU 40A)
Straight-Through Wiring, Replaces 1-1.5 Pole Devices Used Primarily in Residential Central Air Conditioning
FEATURES
.Replaces many type 117 contactors used by OEM's
.Universal style mouting bracket fits existing mounting holes
.Screw terminals and 1/4 quick connect terminals for easy installation.
Specifications
| Temperature Range | -40°F to 150°F | ||||||
| Mechanical Life(No load) | Conforms to UL and ARI Specifications | ||||||
| Electrircal Life | Conforms to UL and ARI Specifications 94-388 thru 94-390 achieve 200,000 Cycles,make LRA at.5pf, break 125% of FLA at. 75pf at rated voltage,10,000 cycles make and brek LRA at.5pf rated voltage 94-394 thru 94-369 achieve 100,000 cycles, make LAR at 5pf at rated voltage 6.000 cycles make and break LEA at 5pf rated voltage | ||||||
| Weight(approximate) | 9.25 oz | ||||||
| Coils Frequency | 50/60HZ | ||||||
| Coil Insulation | Class B(130°) | ||||||
| Termination | Screw and Double 1/4 Q.C. | ||||||
| Operate | 85% of nominal coil voltage; | ||||||
| 110% maximum safe opreate | |||||||
| Duty Cycle | Continuous | ||||||
Coil data
| Steveco nmuber | Volatge | Ress DC | Current | Nominal | Max. Inrush | ||
| 30 Amp 40Amp | AC | OHMS | MA | VA | VA | ||
| C2-388 C2-394 | 24 | 16.5 | 208 | 5 | 20 | ||
| C2-389 C2-395 | 120 | 420 | 42 | 5 | 20 | ||
| C2-390 C2-396 | 208/240 | 1825 | 21 | 5 | 20 | ||
Contact Ratings
| Type | Voltage | FLA | LRA | RES | |||
| C2-388 thru C2-390 | 277 | 30 | 150 | 40 | |||
| 480 | 30 | 75 | 40 | ||||
| 600 | 30 | 50 | 40 | ||||
| C2-384 thru C2-396 | 277 | 40 | 200 | 50 | |||
| 480 | 40 | 100 | 50 | ||||
| 600 | 40 | 80 | 50 | ||||